AERO_aH Print

Features

Air equipment for controlled change of air integrated dehumidification control
concurring to DIN1946-6(2006): Design and dimensioning of residential ventilation systems

connectivity:
  • climatic sensor IN (T,rH): Vb=5V, digital out
  • climatic sensor OUT(T,rH): Vb=5V, digital out
  • power supply: 12V DC
  • cooling pipe on the rear side
Measuring range climatic sensors:
  • inside: 0..100%rF -20..+80°C
  • outside: 0..100%rF -20..+80°C
  • precision T: +/-0,2°C
  • precision rH: +/-2%
General functions:
  • simultaneous ventilations IN and OUT
  • heat recovery
  • filtration of air (input and output)
  • ventiduct with weather protection

Modes

Manual mode:
The fresh air is drawn in from the outside by the blast working in the appliance, conducted over the heat exchanger and supplied into the room by 3 adjustable ventiducts. The air capacity performance (swept volume) is directly adjustable by a turning knob. Additionally the increased air capacity performance for the automaticly mode can be programmed by the turning knob.
Automatic mode:
At this the absolutes humidity values aH OUT and aH IN are permanently calculated according to the measured outside and inside climate values (rH, t). The blast switches automaticly in the increased (programmed) air capacity, if aH IN > aH OUT and if the measured inside relativ humidity exceed the adjusted humidity (e.g.50%). In this mode the turning knob serves for the adjustment of the wished humidity.

Download Datasheet