Publikationen CAN-BUS
Startseite | CAN-Bus | TSL - CAN - 03
TSL-CAN-03 Print
Criteria

Parameter
  • temperature range: -40...+80 °C
  • accuracy: ±0,3 K (10...80 °C)
  • technology: semiconductor
  • Resolution: 0,1 K
  • Scanning density: >= 5 ms
Protocol
  • CAN-Protocol: CANopen 2.0 A, by CiA DS 404
  • Physical Layer: by ISO 11898
  • Supply Voltage: 10...48 V DC
Operating Conditions
  • ambient temperature: -40 °C bis +80 °C
  • storage temperature: -40 °C bis +120 °C
  • Shock strenght: 30 g, in 14 ms at RT
  • Vibration stability: 10 g bei 20-1000 Hz
  • EMV and ESD checked: EN 50082-1 und EN 50082-2
  • For the measuring least air speed needed crossways to the Sensor 1,5 m/s

CAN-Bus Temperature-Sensor TSL-CAN-03 (Air type)

Applications

This temperature sensor enable the mearuring of temperature in indoor - and outdoor area under defined operation conditions
  • archive monitoring
  • room air conditioning
  • weather stations
  • etc.
Electrical connection:
5-poliger Binder-connector M12x1 (male)by CiA DR-303-1