Criteria

Measuring range humidity: 0...100 % rel. humidity
  • accuracy: ±2 % (10...90 % r.h.)
  • response time: < 4 sec
  • measuring element capacitiv, dewing strength
Measuring range temperature: -40...+80 °C
  • accuracy: ±0,5 K (5...40 °C)
  • response time: < 20 sec
  • measuring element semiconductor
Measuring parameter
  • measuring resolution: 12 Bit
  • scanning density min. 5 ms
Protocol- and connection data:
  • CAN-Protocol: CANopen 2.0A, CiA DS 404
  • physical Layer: ISO 11898
  • operating voltage: 10...48 V DC
Operating condition:
  • ambient operating temperat. -40 to +80 °C
  • storage temperature -40 to +120 °C
  • EMV and ESD checked: EN 50082-1, EN 50082-2
  • for the measuring least air speed needed crossways to 1,5 m/s
    the sensor

CAN-Climatic-Sensor KS-CAN-02

Applications

This climate sensor enable the measuring of the humidity and temperature in in-door- and out-doorarea under defined operating condition
  • archiv monitoring
  • room air conditioning
  • weather stations
Attachments:
 CAN-BUS Klimasensor KS-CAN03[deutsch]138 Kb
 CAN-BUS climate sensor KS-CAN03[englisch]137 Kb